为将电介质频率响应法推广应用于变压器绝缘状态评估,利用电介质频率响应法对110 kV及220 kV油浸式变压器高压-低压套管之间的油纸绝缘系统进行电介质响应测试;建立RC弛豫模型解析变压器油纸绝缘体系的绝缘性能,并通过最佳优化方法获得模型参数。结果表明:良好的绝缘体系使得各支路绝缘电阻增大,时间常数减小。
In order to apply dielectric frequency response method to assess the transformer insulation condition, we used dielectric frequency response method to measure the dielectric response of oil-paper insulation system between high voltage and low voltage bushings of 110 kV and 220 kV oil-immersed transformers. A RC relaxation model was established to analyze the insulating properties of the transformer oil-paper system, and the model parameters were obtained by the best optimization method. The results show that the good insulation system would make insulation resistance in each branch increase and the time constant decrease.
参考文献
[1] | Wang M, Vandermaar A J, Srivastava K D . Review of Con-dition Assessment of Power Transformers in Service[J].IEEE Electrical Insutation Magazine,2002,18(6):12-25.,2002. |
[2] | Lundgaard L E, Hansen W, Linhjell D, el al . Aging of Oil-impregnated Paper in Power Transformers[J].IEEE Transaltions on Power Delivery,2004,19(1):230-239.,2004. |
[3] | 刘君,吴广宁,周利军,闵英杰,吕玮.油纸绝缘体系微水扩散的分子模拟[J].高电压技术,2010(12):2907-2912. |
[4] | Saha T K, Yao Z T . Experience with Return Voltage Mea-surements for Assessing Insulation Conditions in Ser-vice-aged Transformers[J].IEEE Transactions on Power De-livery,2003,18(1):128-135.,2003. |
[5] | 王林,彭倩,周利军,姚晓,赵赢峰,甘德刚.油纸绝缘老化特性的回复电压分析[J].绝缘材料,2012(05):42-45. |
[6] | Saha T K, Purkait P . Investigation of Polarization and Depolarization Current Measurements for the Assessment of Oil-paper Insulation of Aged Transformers[J].IEEE Transal-tions on Dielectrics and Electrical Insulation,2004,11(1):144-154.,2004. |
[7] | 李大建,王林,周利军,吴广宁,李先浪,李延涛.变压器油纸绝缘极化电流特性影响因素的分析[J].绝缘材料,2013(04):75-78. |
[8] | Linhjell D,Lundgaard L . Dielectric Response of MineralOil Impregnated Cellulose and the Impact of Aging[J].IEEE Transactions on Dielectrics and Electrical Insulation,2007,14(1):156-169.,2007. |
[9] | Liu J, Zhou L J, Wu G N, et al . Dielectric Frequency Re-sponse of Oil-paper Composite Insulation Modified by Nanoparticles[J].IEEE Transactions on Dielectrics and Elec-trical Insulation,2012,19(2):510-520.,2012. |
[10] | 陈名铭,韦国,刘君,赵赢峰,周利军,吴广宁,朱毅刚,张云.温度和水分对变压器油纸绝缘系统频域介电谱特性的影响[J].绝缘材料,2012(01):57-61. |
[11] | Ekanayake C. Diagnosis of Moisture in Transformer Insulation-application of Frequency Domain Spectroscopy [D]. Gothenburg,Sweden:Chalmers University of Technology, 2006.,2006. |
[12] | Setayeshmehr A, Fofana I, Eichler C, et al . Dielectric Spectroscopic Measurements on Transformer Oil-paper Insulation under Controlled Laboratory Conditions[J].IEEE Transaltions on Dielectrics and Electrical Insulation,2008,15(4):1100-1111.,2008. |
[13] | Fofana I, Hemmatjou H, Meghnefi F, et al . On the Fre-quency Domain Dielectric Response of Oil-paper Insulation at Low Temperatures[J].IEEE Transactions on Dielectrics and Electrical Insulation,2010,17(3):799-807.,2010. |
[14] | Jonscher A K. Dielectric Relaxation in Solids[M]. London:Dielectrics Press Limited,1996:66-110.,1996. |
[15] | 殷之文. 电介质物理学[M]. 北京:科学出版社,2003:57-65.,2003. |
[16] | 赵孔双. 介电谱方法及应用[M]. 北京:化学工业出版社,2008:50-57.,2008. |
[17] | Zhou L J, Wu G N, Liu J . Modeling of Transient Mois-ture Equilibrium in Oil-paper Insulation[J].IEEE Transac-tions on Dielectrics and Electrical Insulation,2008,15(3):872-878.,2008. |
[18] | Lagarias J C, Reeds J A, Wright M H, et al . Convergence Properties of the Nelder-Mead Simplex Method in Low Di-mensions[J].SIAM Journal of Optimization,1998,9 |