通过试验和理论计算对影响发电机定子线棒介质损耗的因素进行了分析,结果表明:发电机定子线棒介质损耗因数(tanδ)的大小与线棒导线绝缘结构、防晕结构、线棒几何尺寸、主绝缘厚度等有关,有端部防晕层的线棒其介质损耗比没有防晕层的线棒大;随着防晕层厚度、主绝缘厚度线棒导体尺寸的增加,介质损耗因数将会减小。

The influence factors of the tanδ of generator stator bar were studied by test and theory calcu-lation. The results show that the dielectric loss factor(tanδ) of generator stator bar is related with the insu-lation structure, anti-corona structure, conductor size and main insulation thickness of the stator bar. The dielectric loss factor of the bar with anti-corona coating at the end is bigger than that of the bar without anti-corona coating. With the increase of anti-corona coating thickness, main insulation thickness and con-ductor size, the dielectric loss factor decreases.

参考文献

[1] 漆临生,梁智明,皮如贵.发电机定子线棒导线绝缘结构试验研究[J].绝缘材料,2005(03):19-25,28.
[2] 张百华,高乃奎,马小芹,谢恒堃.基于运行历史的大电机主绝缘老化特性的研究[J].中国电机工程学报,2004(08):134-137.
[3] 隋银德,傅岚贵.高压电机定子线圈电场分布的改善[J].大电机技术,2001(02):22-25.
[4] 严璋;朱德恒.高电压绝缘技术[M].北京:中国电力出版社,2002:173-245.
[5] 邱昌容;曹晓珑.电气绝缘测试技术[M].北京:机械工业出版社,2004:27-105.
[6] 张良莹;姚熹.电介质物理[M].西安:西交大出版社,1991
[7] Hu C;Yuan X;He X.Study on the Effect of Differ-ent Internal Corona Protection on Electrical Properties of Generator Stator Bar[A].Harbin,China,2009
[8] 仲伟堂,丛喜宾.发电机电晕现象分析及处理[J].辽宁工学院学报(自然科学版),2003(01):50-51,59.
[9] 张瑞钧;刘上椿.高压大型汽轮发电机定子线圈主绝缘结构优化设计[J].大电机技术,1997(04):31-36.
[10] Goffaux R .The Essence of High Voltage Insulation Dielec-tric Loss[J].IEEE Transactions on Electrical Insulation,1978,1(01):1-13.
[11] JB/T 7608-2006.测量高压交流电机线圈介质损耗角正切试验方法及限值[S].北京:机械工业出版社,2006.