欢迎登录材料期刊网

材料期刊网

高级检索

The influence of chloride or sulphur dioxide on the corrosion behavior of copper tube in the air-conditioning system was studied using scanning electron microscope (SEM), energy dispersion spectrometer (EDS) and cyclic polarization techniques. The results showed that the corrosion of copper tube are mainly caused by the SO4 and Cl ions in the circulating water, and the former is mainly responsible for the general corrosion of the copper tube whilst the latter for the pitting corrosion. The di®erent in°uences of SO4 and Cl ions on the corrosion type of copper tube may be attributed to that the radius of SO4 ion is much larger than that of Cl ion. Meanwhile the results also indicated that SO4 inhibits the pitting corrosion caused by Cl and Cl inhibits the general corrosion initiated by SO4 due to their competitive adsorption on the copper matrix.

参考文献

[1]
[2]
上一张 下一张
上一张 下一张
计量
  • 下载量()
  • 访问量()
文章评分
  • 您的评分:
  • 1
    0%
  • 2
    0%
  • 3
    0%
  • 4
    0%
  • 5
    0%