本文构建实施了一种适用于高温高湿气候的单转轮两级太阳能除湿空调系统.该系统主要由一台5 kW单转轮两级除湿空调机组和15 m2真空管空气集热器组成.通过实验测试对其运行特性进行了研究.结果表明,单转轮两级太阳能除湿空调不仅可以有效地实现温湿度处理,提供舒适的空调送风,而且具有良好的热力和电力性能.测试时间内系统制冷量在2.67~4.24 kW之间,相应平均除湿量为8.36 g·kg-1,平均热力COP接近1.0,考虑输配用电的平均电力COP达4.65.此外,该系统可将50%左右的太阳辐射能量转变为空调能力输出.
参考文献
[1] | Jerry Wurm;Douglas Kosar;Tom Clemens .Solid Desiccant Technology Review[J].Bulletin de l'Institut International du Froid,2002(3):2-31. |
[2] | D. La .Technical development of rotary desiccant dehumidification and air conditioning: A review[J].Renewable & sustainable energy reviews,2010(1):130-147. |
[3] | R. Z. Wang;T. S. Ge;C. J. Chen;Q. Ma;Z. Q. Xiong .Solar sorption cooling systems for residential applications: Options and guidelines[J].International Journal of Refrigeration,2009(4):638-660. |
[4] | T.S. Ge;Y.J. Dai;R.Z. Wang;Y. Li .Experimental Investigation On A One-rotor Two-stage Rotary Desiccant Cooling System[J].Energy,2008(12):1807-1815. |
[5] | T. S. Ge;Y. Li;R. Z. Wang;Y. J. Dai .Experimental study on a two-stage rotary desiccant cooling system[J].International Journal of Refrigeration,2009(3):498-508. |