针对某110 kV变电站10 kV变低管型母线在红外测温过程中2#主变B相变低管型母线出现测温异常的情况,采用常规停电方法测量具有一定的局限性,通过采用脉冲电流局放检测法及极性定位法查明缺陷原因,并解体进一步验证试验及分析结果。结果表明:10 kV管型母线的绝缘电阻、介质损耗及电容量、回路电阻等常规测试手段在绝缘受潮初期检测过程中具有一定的局限性,脉冲电流局放检测法能很好地弥补这些不足,可以在10 kV管型母线的检测中推广使用。

In view of the abnormal situation of 2# main transformer B phase tubular busbar found in the infrared temperature measurement process of 10 kV tubular busbar in an 110 kV substation, because con-ventional outage measurement method has certain limitation, we used pulse current partial discharge detec-tion method and polar localization method to find the cause and further verified the test results by disas-sembly. The results show that the insulation resistance, dielectric loss and capacitance, loop resistance and other conventional test methods have some limitations in the early stage of insulation moistened, and the pulse current partial discharge detection method can remedy these shortcomings well, which can be ex-tended to use in detection of 10 kV tubular busbar.

参考文献

[1] 郑云海,吴奇宝,何华琴,王门鸿.全绝缘管母线局部放电的检测与分析诊断[J].绝缘材料,2010(04):63-66.
[2] 陈永武.铜管屏蔽绝缘母线的特点和应用[J].硫磷设计与粉体工程,2007(06):35-38.
[3] 谭美燕.大容量主变低压侧母线的选择--优选绝缘铜管母线[J].沿海企业与科技,2010(10):122-124,121.
[4] 唐庆华,陈荣,郭浩,李进,刘宝成,李武兴,杜伯学.热缩母排套管自然老化后的电气和力学性能研究[J].绝缘材料,2013(04):55-58,62.
[5] 金月新,张彩霞.绝缘电阻的测量[J].沈阳工程学院学报(自然科学版),2009(01):59-61.
[6] 陈天翔;王寅仲.电气试验[M].北京:中国电力出版社,2006
[7] 钟定珠,孙旭,罗志昭.变电站新型绝缘铜管母线[J].广东输电与变电技术,2005(02):69-70.
[8] 关芳,杨益民.管型屏蔽绝缘母线的应用[J].中国水能及电气化,2011(05):59-62.
[9] Gulshi E;Cicheki P;Wester F et al.On-site Testing and PD Diagnosis of HV Power Cables[J].IEEE Transactions on Dielectries and Electrical Insulation,2008,15(6):1691-1700.
[10] 王俊波,胡聪,李国伟,张伟忠.10 kV绝缘铜管母线沿面放电特性研究[J].绝缘材料,2013(04):79-81,85.
[11] Y. Tian;P. L. Lewin;A. E. Davies;S. J. Sutton;S. G. Swingler .Partial discharge detection in cables using VHF capacitive couplers[J].IEEE transactions on dielectrics and electrical insulation: A publication of the IEEE Dielectrics and Electrical Insulation Society,2003(2):343-353.
[12] 陈化刚.电力设备预防性试验技术问答[M].北京:中国水利水电出版社,1998
[13] 郭灿新,张连宏,姚林朋,钱勇,黄成军,江秀臣.局部放电HF/UHF联合分析方法的现场电缆终端检测应用[J].电力自动化设备,2010(05):92-95.
[14] 陈璐,姚林朋,钱勇,刘君华,黄成军,江秀臣.XLPE电缆中间接头局部放电电磁波特性仿真分析[J].高压电器,2010(10):27-31.
[15] 陈化钢.电气设备预防性试验方法[M].北京:中国水利水电出版社,1994
[16] 李海烽.大容量主变压器10kV侧导体的合理选择——(半)绝缘式铜质管形母线[C].输配电及电力系统专业论文集2003年第6辑,2003:41-45.
[17] 梁之林,张万林,王刚.电气设备导电回路电阻测试方法及控制标准探讨[J].吉林电力,2008(02):23-25.
[18] 丁毓山;徐义斌;王向臣.电气试验工[M].北京:中国水利水电出版社,2009
[19] Katsuta G.;Toya A. .Development of a method of partial discharge detection in extra-high voltage cross-linked polyethylene insulated cable lines[J].IEEE Transactions on Power Delivery,1992(3):1068-1079.
上一张 下一张
上一张 下一张
计量
  • 下载量()
  • 访问量()
文章评分
  • 您的评分:
  • 1
    0%
  • 2
    0%
  • 3
    0%
  • 4
    0%
  • 5
    0%