在变电站高压设备巡视中通过红外检测发现运行中的110 kV主变压器套管局部发热异常.综合应用红外、紫外成像和超声波局放检测技术诊断瓷套管存在裂纹或污秽缺陷.停电检查套管发现其表面积污严重,部分伞裙有明显的放电痕迹.分析认为引起发热和局部放电异常的原因是瓷套管表面污秽受潮.对瓷套管表面进行喷涂PRTV涂料处理后,套管带电检测数据正常,消除了套管缺陷,并提出了防污闪的建议.
An operating 110 kV transformer bushing was found abnormal local heating by infrared detec-tion in the inspection of transformer substation equipment; and crack or pollution defects were indicated in the porcelain bushing through comprehensive diagnoses of infrared, ultraviolet imaging and ultrasound PD detection technique. The surface of the bushing was found seriously polluted, and part of the umbrel-la skirt had obvious discharge tracks. It is analyzed that heating and partial discharge are caused by the porcelain bushing’s surface pollution and wetness. After spraying PRTV coating on the porcelain bushing surface, the charged detection data restore normal condition and the defects are eliminated. Some anti-pol-lution suggestions are then put forward.
参考文献
[1] | 郑伟,郑新才,黄梅,杨素梅.输变电设备防污闪措施比较和分析[J].电气应用,2010(05):68-70. |
[2] | 喻华玉,徐文澄.防污闪技术分析[J].电力安全技术,2005(03):28-30. |
[3] | 张淑静,刘志林,车传强,文惠君.紫外成像技术在变电站带电检测中的应用[J].内蒙古电力技术,2006(06):26-27. |
[4] | 张彦涛,王绍华,马晟.基于超声波技术的绝缘子污秽放电检测方法[J].山西电力,2010(03):32-34. |
[5] | Q/CSG114002-2011.电力设备预防性试验规程[S]. |
[6] | DLT 664-2008.带电设备红外诊断应用规范[S]. |
[7] | 毕自治.变电站绝缘设备的污闪及防治措施[J].科技创新导报,2010(10):68-68. |
[8] | 李佐胜,姚建刚,杨迎建,陈芳,金永顺,苗增强.湿污绝缘子发热模型[J].电工技术学报,2009(07):21-27. |
[9] | 李璐,郑彦琴,许东升.电力设备防污闪涂料的应用与施工[J].供用电,2007(04):31-33,39. |
[10] | 钟庆东,尧华,祝铭,姚政.防污闪涂料的防污闪机理研究进展及应用[J].上海电力学院学报,2005(03):271-274. |
[11] | 张亚龙.RTV防污闪涂料在输电线路及变电站的应用[J].陕西电力,2006(06):44-46. |