为了研究微肋管结构尺寸及工况等对管内流动蒸发及冷凝性能的影响,对3根管外径为9.52 mm和2根外径为7 mm的微肋管进行了蒸发及冷凝实验,所用工质为R22.所选工况为,45℃冷凝温度,30~45℃的入口过热度,2℃的出口过冷度,7℃蒸发温度,15%~20%的入口干度,5~6℃的出口过热度,实验中质量流速变化范围为90~500kgm-2s-1.获得了换热性能随质量流速的变化,讨论了微肋结构尺寸对蒸发换热和冷凝换热性能的影响.
参考文献
[1] | Schlager L M;Pate M B;Bergles A E .Evaporation and Condensation Heat Transfer and Pressure Drop in Horizontal 12.7 mm Microfin Tubes with Refrigerant 22[J].Journal of Heat Transfer,1990,112:1041-1047. |
[2] | Chamra L M;Webb R L .Advanced Micro-fin Tube for Evaporation[J].International Journal of Heat and Mass Transfer,1996,39(09):1827-1838. |
[3] | K. Seo;Y. Kim .Evaporation heat transfer and pressure drop of R-22 in 7 and 9.52 mm smooth/micro-fin tubes[J].International Journal of Heat and Mass Transfer,2000(16):2869-2882. |
[4] | 吴晓敏,王晓亮,王维城.水平微肋管内流动蒸发换热特性的实验研究[J].化工学报,2003(09):1215-1219. |
[5] | 吴晓敏,王晓亮,王维城.水平新型微肋管内流动冷凝换热及流阻特性[J].上海理工大学学报,2003(04):326-329. |