  为研究不同环境因素下油纸绝缘极化电流特性变化规律,搭建了油纸绝缘极化电流特性测试系统,应用该系统测试了不同温度、水分和油隙下油纸绝缘体系的极化电流特性,并通过参数拟合法进行了曲面拟合。结果表明:温度升高,极化电流增大,温度主要通过影响油纸绝缘弛豫时间而影响极化电流特性;水分含量增加,极化电流增大,绝缘油和绝缘纸的直流电导率分别与油中和纸中的水分含量呈指数关系,通过极化电流法可直接得到油中和纸中的水分含量;油隙增大,极化电流初值减小,终值增大,油隙是影响油纸绝缘极化电流特性的一个不可忽略的因素,在测试分析过程中予以重视。

To study the change law of polarization current characteristic under various environmental fac-tors, a test system was built to test the polarization current characteristic of oil-paper insulation under var-ious temperatures, moisture content and oil gap, and then the results was fitted by parameter fitting meth-od. The results show that with the increase of temperature, the polarization current increases, which is af-fected by the relaxation time influenced by temperature. With the increase of moisture content, the polar-ization current increases, the DC conductivity of the insulating oil and insulating paper shows an exponen-tial relationship with the moisture content in the oil and paper respectively, and the moisture content in the oil and paper can be directly obtained by the polarization current method. With increase of oil gap, the initial value of the polarization current decreases and the final value increases, the oil gap is a non-negligible influencing factor of the polarization current of oil-paper insulation, which should be taken seriously in test and analysis process.

参考文献

[1] Lars E. Lundgaard;Walter Hansen;Dag Linhjell;Terence J. Painter .Aging of Oil-Impregnated Paper in Power Transformers[J].IEEE Transactions on Power Delivery,2004(1):230-239.
[2] 周利军,吴广宁,宿冲,王洪亮.变压器油中故障气体的复合预测方法[J].西南交通大学学报,2006(02):150-153.
[3] 陈名铭,韦国,刘君,赵赢峰,周利军,吴广宁,朱毅刚,张云.温度和水分对变压器油纸绝缘系统频域介电谱特性的影响[J].绝缘材料,2012(01):57-61.
[4] Bhumiwat S A.On-site Non-destructive Diagnosis of In-ser-vice Power Cables by Polarization/Depolarization Current Analysis[A].San Diego,US,2010:1-5.
[5] 吕玮,吴广宁,周利军,刘君,王韬.基于频率响应油纸绝缘系统微水状态研究[J].绝缘材料,2011(02):67-70.
[6] 王林,彭倩,周利军,姚晓,赵赢峰,甘德刚.油纸绝缘老化特性的回复电压分析[J].绝缘材料,2012(05):42-45.
[7] Leibfried T;Kachler A J.Insulation Diagnostics on Power Transformers Using the Polarisation and Depolarisation Cur-rent (PDC) Analysis[A].Bos-ton,USA,2002:170-173.
[8] Gradnik T;Babuder M;Koncan-Gradnik M.Estimation of Water Content in Power Transformers in Service by Polar-ization and Depolarization Current Measurements[A].,2008:1-4.
[9] Saha T K;Purkait P.Impact of the Condition of Oil on the Polarisation based Diagnostics for Assessing the Condi-tion of Transformers Insulation[A].,2005:1882-1886.
[10] T. K. Saha;P. Purkait .Understanding the Impacts of Moisture and Thermal Ageing on Transformer's Insulation by Dielectric Response and Molecular Weight Measurements[J].IEEE Transactions on Dielectrics and Electrical Insulation,2008(2):568-582.
[11] Tapan K. Saha;Prithwiraj Purkait .Investigation of an Expert System for the Condition Assessment of Transformer Insulation Based on Dielectric Response Measurements[J].IEEE Transactions on Power Delivery,2004(3):1127-1134.
[12] S. M. Gubanski;P. Boss;G. Csepes;V. Der Houhanessian;J. Filippini;P. Guuinic;U. Gafvert;V. Karius;J. Lapworth;G. Urbani;P. Werelius;W. Zaengl .Dielectric response methods for diagnostics of power transformers[J].IEEE Electrical Insulation Magazine,2003(3):12-18.
[13] A. V. Mamishev;Y. Du;J. H. Bau;B. C. Lesieutre;M. Zahn .Evaluation of diffusion-driven material property profiles using three-wavelength interdigital sensor[J].IEEE transactions on dielectrics and electrical insulation: A publication of the IEEE Dielectrics and Electrical Insulation Society,2001(5):785-798.
[14] 周凯,吴广宁,何景彦,刘君,佟来生.脉冲电压下局部放电信号的提取和统计[J].西南交通大学学报,2008(03):319-324.
[15] Garcia B.;Burgos J.C.;Alonso A.M.;Sanz J. .A moisture-in-oil model for power transformer monitoring - Part II: Experimental verification[J].IEEE Transactions on Power Delivery,2005(2):1423-1429.
[16] Ildstad E;Gafvert U;Tharning P.Relation Between Return Voltage and Other Methods for Measurements of Dielectric Response[A].Pittsburg,USA,1994:25-28.
[17] Gafvert U;Adeen L;Tapper M.Dielectric Spectros-copy in Time and Frequency Domain Applied to Diagnos-tics of Power Transformers[A].China,2000:825-830.
[18] T. K. Saha;P. Purkait .Investigation of Polarization and Depolarization Current Measurements for the Assessment of Oil-paper Insulation of Aged Transformers[J].IEEE transactions on dielectrics and electrical insulation: A publication of the IEEE Dielectrics and Electrical Insulation Society,2004(1):144-154.
[19] 周利军,汤浩,吴广宁,王云飞.油纸绝缘微水扩散的稳态分布[J].高电压技术,2007(08):27-30.
[20] Coelho R.Physics of Dielectrics for the Engineer[M].Am-sterdam,Holland:Elsevier Scientific Publishing Company,1979
[21] JONSCHER A K.Universal Relation Law[M].London,UK:Chelsea Dielectric Press,1996
[22] Jonscher A K.Dielectric Relaxation in Solids[M].London,UK,Chelsea:Dielectrics Press Limited,1996
[23] Du Y;Mamishev A V;Lesieutre B C.Measurement of Moisture Diffusion as a Function of Temperature and Moisture Concentration in Transformer Pressboard[A].Atlanta,USA,1998:341-344.