本文提出了以HFC-161混合物作为HCFC-22的新型替代制冷剂(HFC-161/125/32,15/42.5/42.5wt%),并在设计使用R410A的压缩机性能测试台上,进行了该混合制冷剂与R410A在若干工况下的性能对比实验.实验结果表明,该新制冷剂的COP略高于R410A,而排气温度略低于R410A.与R410A相比,该新制冷剂的蒸发压力和冷凝压力均低约10%,制冷量和压缩机功耗分别下降4.3%和4.8%.该混合制冷剂物性环境性能良好,ODP为零,GWP值小于R410A.可作为HCFC-22的较为理想的替代制冷剂之一.
参考文献
[1] | Dongsoo Jung;Yongjae Song;Bongjin Park .Performance des melanges de frigorigenes utilises pour remplacer le HCFC22[J].International Journal of Refrigeration,2000,23:466-474. |
[2] | Mark W. Spatz;Samuel F. Yana Motta .An evaluation of options for replacing HCFC-22 in medium temperature refrigeration systems[J].International Journal of Refrigeration,2004(5):475-483. |
[3] | Yongmei Xuan;Guangming Chen .Experimental study on HFC-161 mixture as an alternative refrigerant to R502[J].International Journal of Refrigeration,2005(3):436-441. |
[4] | Calm J M;Hourahan G C .Refrigerant data summary[J].Engnr Sys,2001,18:74-88. |
[5] | NIST(National Institute of Standard Technology) Standard Reference Database 23,Version 7.0[Z].,2002. |